Get a Quote
Home/Blog/Wire Gauge Guide
Reference guide

Wire Gauge and Cable Sizing Guide for Lighting Exporters

Conductor sizes from 0.75 to 10 mm2 against their AWG equivalents, the ampacity and drop rules that size them, and the cable specs that appear in export inspections.

2026-09-10 · 6 min read · Reference guide

Colorful electrical cables neatly arranged on a dark workbench

Cable size is where lighting quotations quietly carry risk. Under-specify the conductor and a project fails inspection or, worse, runs hot behind a ceiling; over-specify and every metre of every circuit costs more than it should. This guide collects the sizing reference that export projects argue about most: the mm²-to-AWG translation between metric and North American drawings, typical ampacity by conductor size, and the low-voltage drop arithmetic that governs LED strip runs. All ampacity values are illustrative for common PVC/XLPE building cable in typical installation conditions — the prevailing local code (IEC 60364-5-52, NEC, AS/NZS 3000 and their national variants) always governs the final selection.

Conductor size reference: mm², AWG and lighting use

Conductor (mm²)AWG equivalentTypical ampacity (illustrative)Typical lighting use
0.5203-4 AInternal luminaire wiring, small fittings
0.75186 AFlexible cords for portable and decorative lamps
1.01710 AShort drops, small lighting circuits
1.51610-16 AStandard lighting circuits, EU residential and commercial
2.51416-20 ASocket circuits, driver feeds on long runs
4.01225-32 ASub-mains, high-bay and industrial feeders
6.01032-40 ADistribution feeders, large installations
10.0843-55 AMains distribution, central driver rooms

Illustrative values for copper conductors at 70-90°C insulation in typical enclosed installation conditions. Derating for grouping, ambient temperature and insulation class is code-specific — size with the local standard, not this table alone.

Low-voltage drop: the strip-light problem

Mains circuits rarely stress cable size — a 100W flood draws under half an amp at 230V. Low-voltage strip is different: the same 100W at 24V draws over 4 A, and at 12V over 8 A, so voltage drop across the run becomes the real constraint. Keep drop below 3% on low-voltage runs (and total circuit drop under 5% including mains side) or the far end visibly dims and shifts colour.

Strip runLoadCurrentRecommended conductorPractical outcome
24V, 5 m48 W2 A0.75-1.0 mm²Drop under 2% — standard feed fine
24V, 10 m96 W4 A1.5-2.5 mm²Feed from both ends to be safe
12V, 5 m48 W4 A1.5 mm²Workable; 24V preferred
12V, 10 m96 W8 A2.5-4.0 mm²Inject power at both ends or re-spec to 24V

Illustrative single-feed figures. Beyond about 5 m, the cheapest fix is usually a higher-voltage system (24V over 12V, or constant-current 48V for long lines), not thicker copper.

What export buyers should check on cable specs

  • Copper, not copper-clad aluminium. CCA conductors read the same gauge on the jacket and cost less — and run hotter, break at terminations and fail code in most export markets. Ask for the conductor material in writing.
  • Harmonised codes tell the story. H05VV-F and H05RN-F are 300/500V flexible cords; H07RN-F is 450/750V rubber for outdoor duty. A quotation that says "PVC cable" with no harmonised number has not specified anything.
  • Insulation temperature rating matters in fixtures. Luminaire internal wiring near the source often needs 90°C or 105°C rated silicone or PTFE, not generic 70°C PVC — one of the first things labs check in EN 60598 testing.
  • AWG and mm² are not exact twins. 1.5 mm² is slightly smaller than 16 AWG; on international projects, size to the stricter of the two drawings rather than assuming equivalence.
  • Drivers change the load. Inrush and power factor matter on long circuit runs with many drivers; a circuit that passes ampacity can still trip on inrush — split the feeds rather than upsizing blindly.

Cable in the product line

Industrial and outdoor lines carry the heaviest cable decisions: feeder sizing for high-bay banks under industrial lighting, rubber-jacketed and UV-stable supply cable for outdoor and solar lighting (where the solar sizing arithmetic also sets battery-to-lantern cable runs, per our solar sizing guide), and fire-performance requirements on commercial circuits under commercial lighting. State conductor material, harmonised cable code and insulation class on the inquiry and the BOM comes back auditable — which is what inspectors, and ten-year warranty claims, actually read.

Common questions

Wire gauge FAQ

Is 1.5 mm² enough for a lighting circuit?
For typical residential and commercial lighting in IEC-territory markets, yes — 1.5 mm² copper on a 10-16 A protective device is the standard lighting circuit and carries far more than most LED loads need. Long commercial runs with many drivers, or North American AWG-based drawings, should still be checked against the local code's derating and voltage-drop rules.
What is 18 AWG in mm²?
18 AWG is approximately 0.82 mm², sitting just above the 0.75 mm² harmonised size — which is why 18 AWG lamp cords and 0.75 mm² flexible cords behave similarly in practice. The systems are close but not identical, so match the stricter drawing when a project mixes both conventions.
Why does my LED strip dim at the far end?
Voltage drop. At 12V, even a few metres of thin feed cable loses enough voltage to dim and warm-shift the far end of the run. Fix it by feeding from both ends, shortening runs, moving to 24V, or stepping up conductor size — in that order of cost. The low-voltage table above gives the typical sizing per run length.
Keep reading

Related articles

Need the BOM cable specs in writing?

Conductor material, harmonised codes and insulation class stated on every quotation — send the project and get the auditable BOM within 24 hours.

Start an inquiry